Home / Product / Type MC (Metal Clad Cable)



Lightweight Aluminum Interlocked Armor. 600 Volts.
Copper Power Conductors. THHN/THWN Insulated Singles.
Green Insulated Grounding Conductor.
Sizes 14 AWG through 2 AWG. Rated VW-1
Type MC Cable is suitable for use as follows:
multi-residential buildings.
Type MC Cable meets or exceeds the requirements of the following
• UL 83
• UL 1569
• UL 1685
• Federal Specification A-A59544 (formerly J-C-30B)
• FT4/IEEE 1202 (70,000 Btu/hr) Vertical Cable Tray Flame Test
• NEC
• Listed for use in UL 1, 2 and 3 Hour Through Penetration Firestop Systems
Type MC Cable is constructed with soft-drawn copper, Type THHN/THWN conductors rated 90°C dry available in sizes 14 AWG through 2 AWG, and a green insulated grounding conductor. The conductors are cabled together and a binder tape bearing the print legend is wrapped around the assembly. Aluminum interlocking armor is applied over the assembly.
| Conductor | Electrolytic Compressed aluminum class 2 or copper class 2 (Soft Copper or 1350-H19 aluminum) |
| Conductor screen | Semi conductive extruded layer |
| Insulation | TR-XLPE |
| Insulation screen | Semi conductive extruded layer, Easy strippable |
| Copper screen | Copper wires or copper tape |
| Outer sheath | Sun resistant LLDPE sheath |
| Rated voltage (U) | 5~35 kV |
| Identification | Manufacturer’s Name, UL Mark, Type of Insulation, Insulation Level, Wire Size and Type, Rating and UL FILE No. Will be imprinted on the outer insulation jacket of the cable. |
| Conductor | Solid or | Grounding Conductor Size | Overall Diameter | Weight | Ampacity (Amps) | ||
| Size+ (AWG) | Stranded | (AWG) and Stranding | (inches) | (lbs./1000ft.) | 60C | 75C | 90C |
| 14-2 | Solid | 14- 1 | 0.433 | 100 | 15 | 15 | 15 |
| 12-2 | Solid | 12- 1 | 0.469 | 129 | 20 | 20 | 20 |
| 12-3 | Solid | 12- 1 | 0.501 | 157 | 20 | 20 | 20 |
| 12-4 | Solid | 12- 1 | 0.537 | 187 | 20 | 20 | 20 |
| 10-2 | Solid | 10- 1 | 0.537 | 181 | 30 | 30 | 30 |
| 10-3 | Solid | 10- 1 | 0.577 | 225 | 30 | 30 | 30 |
| 10-4 | Solid | 10- 1 | 0.622 | 270 | 30 | 30 | 30 |
| 8-3 | 7 | 10-7 | 0.706 | 320 | 40 | 50 | 55 |
| 8-4 | 7 | 10-7 | 0.754 | 408 | 40 | 50 | 55 |
| 6-3 | 7 | 8-7 | 0.785 | 471 | 55 | 65 | 75 |
| 6-4 | 7 | 8-7 | 0.862 | 580 | 55 | 65 | 75 |
| Note: Ampacity are based on Table 310.16 of the NEC, 2008 Edition. Allowable ampacities shown are for general use as specified by the National Electrical Code, 2008 Edition, Section 310.15. | |||||||
Please contact engineer to Get complate specification.
Please do not hesitate to contact our cable engineer, they will be back to you in next 8 hours.