Home / Product / Medium voltage XLPE or PVC insulated power cable

APPLICATION

It is used to transmit and distribute power in power transmission and distribution system of 35kV or lower. It is generally applied to the fields including power, construction, mines, metallurgy, petrochemical industry and communication in complete replace of oil immersed paper insulated power cable and in partial replace of PVC insulated power cable. Power cables for power networks, underground, outdoors and in cable ducting

Operating characteristics

– Rated power-frepuency voltage U0/U: 3.6/6kv~26/35kv.
– Max.admissible operating temperature of the conductor:90℃.
– Max. short-circurt temperature of conductor shall not exceed 2500C. (5s maximum duration)
– The ambient temperature under installation should not below 00C.
– The bending radius of a single-core cable should not less than 20 times of the cable diameter.
The bending radius of a multi-core cable should not less than 15 times of the cable diameter.

其他 (1)

STANDARD & REFERENCES

IEC 60502-2. Or BS, DIN, ICEA standard as customer request.
IEC 60228
IEC 60332

CONSTRUCTIONS

其他 (3)
Component Specification / Material
Standards IEC 60502-2 or BS6622, BS EN/IEC 60228
Conductor Class 2 stranded plain copper conductor or aluminum conductor
Conductor Screen Semi-conducting material
Insulation XLPE (Cross-Linked Polyethylene) or PVC (Polyvinyl Chloride)
Insulation Screen Semi-conducting material
Metallic Screen Individual and overall copper tape screen
Separator Binding tape
Bedding PVC (Polyvinyl Chloride)
Armoring Single Core: Aluminum Wire Armored (AWA) or Aluminum Tape Armored (ATA)
Multi Core: Steel Wire Armored (SWA) or Steel Tape Armored (STA)
Sheath PVC (Polyvinyl Chloride) or LSZH (Low Smoke Zero Halogen)

PARAMETERS

Type and Name

TypeDesignationApplications
YJVCopper conductor,XLPE insulated,PVC sheathed power cableFor laying indoors,in tunnel or cable trench,unable to bear external mechanical forces.Single core cable is not allowed to laid in magnetic duct.
YJLVAluminum conductor,XLPE insulated,PVC sheathed power cable
YJYCopper conductor, XLPE insulated,PE sheathed power cable
YJLYAluminum conductor, XLPE insulated,PE sheathed power cable
YJV22Copper conductor,XLPE insulated,steel tape armoured,PVC sheathed power cableFor laying indoors,in tunnel in cable trench,or direct in ground,able to bear external mechanical forces.Single core cable is not allowed to laid in magnetic duct.
YJLV22Aluminum conductor,XLPE insulated,steel tape armoured,PVC sheathed power cable
YJV23Copper conductor,XLPE insulated,steel tape armoured,PE sheathed power cable
YJLV23Aluminum conductor,XLPE insulated,steel tape armoured,PE sheathed power cable
YJV32Copper conductor,XLPE insulated,steel wire armoured,PVC sheathed power cableFor laying indoors,in tunnel cable trench,well or direct in ground,able to bear external mechanical forces and certain pulling force.
YJLV32Aluminum conductor,XLPE insulated,steel wire armoured,PVC sheathed power cable
YJV33Copper conductor,XLPE insulated,steel wire armoured,PE sheathed power cable
YJLV33Aluminum conductor,XLPE insulated,steel wire armoured,PE sheathed power cable

Table of the voltage, cores and cross-section

ItemCategory    A 、B3.6/6kV6/10kV8.7/15kV12/20kV18/30kV21/35kV
Category    A 、B6/6kV8.7/10kV12/15kV18/20kV26/35kV
Single coremm225-120025-120035-120050-120050-120050-1200
Three coremm225-40025-40035-40050-40050-40050-400
The cable with Category A rated voltage is used in the situation requiring not over 1 min. of grounding fault lasting time. For the cable with Category B rated voltage, the grounding fault lasting time normally is not over 1 hour, max. lasting time is not over 8 hours, annual ground fault lasting time altogether should not be over 125 hours, Category C includes all the system expect Category A and B.

Please contact engineer to Get complate specification.